First, check these
- Read the room temperature with a probe thermometer and check the controller for the setpoint, a defrost icon or an alarm code.
- Check the door: is it closing fully, is the strip curtain intact, and has it been left open during loading?
- Inside, check the evaporator fans are running and the coil is not a solid block of ice.
- Outside, check the condensing unit fans are spinning, the coil is not blocked by dust, leaves or plastic, and nothing is stacked against it.
- Check the electrical panel for tripped MCBs or a phase-failure or voltage-protection relay showing a fault.
- Check that stock is not stacked against the evaporator or blocking the air throw across the ceiling.
Likely causes
1. Door left open or strip curtain missing
You can check thisSigns: Room warms during loading, fog rolling out of the door, frost around the frame, strips torn off.
Fix: Keep the door shut between trips, repair or replace the strip curtain, and plan loading so the door is not propped open. Fit or repair a door closer.
2. Outdoor condensing unit blocked or overheated
You can check thisSigns: Condensing unit in direct sun, coil dusty, debris or nests in the fins, fans slow or stopped, high-pressure trips on hot afternoons.
Fix: Isolate power and clear loose debris and dust from the coil face. Shade the unit without blocking airflow. Coil washing and fan repairs need a technician.
3. Evaporator iced up
Technician jobSigns: Thick ice on the coil, weak airflow, water or ice under the evaporator.
Fix: A technician should check the defrost heaters, drain line heater, termination sensor and defrost schedule.
4. Airflow blocked by stock
You can check thisSigns: Cartons stacked to the ceiling or against the evaporator, warm pockets at the back of the room.
Fix: Keep a clear space in front of and below the evaporator and leave gaps between stacks and walls so air can circulate.
5. Supply or phase problem
Technician jobSigns: Compressor not running, phase-failure relay tripped, low voltage on one phase, MCB tripped.
Fix: An electrician should check the supply and protection devices. Do not reset repeatedly without finding the cause.
6. Refrigerant leak or component failure
Technician jobSigns: Compressor runs but the room does not cool, partial frost on the coil, oily stains at joints or valves.
Fix: A refrigeration technician must diagnose and repair. Long pipe runs and many joints make leak testing important.
When to call a technician
Call a technician if the room does not start recovering within a couple of hours after you have closed the door, cleared airflow and checked the outdoor unit, if any fan has stopped, if ice keeps returning, or if protection devices trip. Move high-risk stock to other cold storage early; large rooms take many hours to pull down once warm.
Before entering a cold room, make sure the inside door release works and someone knows you are inside. Isolate power before touching any fan or coil. Outdoor units on roofs need safe access. Refrigerant and electrical repairs are for trained technicians only.